Mitsubishi Electric FR-A700 Instruction Manual page 559

Frequency inverter
Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

Parameter
How to find the set frequency for override:
Set frequency [Hz]
Main speed set frequency [Hz]: Terminal 1, 4 or multi-speed setting
Compensation amount [%]: Terminal 2 input
Example
Pr. 73 = 5
The set frequency changes as shown below according to the terminal 1 (main speed) and
terminal 2 (auxiliary) inputs.
Fig. 6-184: Set frequency in dependence on the terminal 1 and terminal 2 signals
When the Pr. 73 setting was changed, check the voltage/current input switch setting. Diffe-
NOTES
rent setting may cause a fault, failure or malfunction. (Refer to page 6-372 for setting.)
The AU signal must be turned on to use the terminal 4.
When inputting compensation to multi-speed operation or remote setting, set "1" (compen-
sation made) to Pr. 28 "Multi-speed input compensation selection". (Initial value is "0".)
FR-A700 EC
Frequency/torque setting by analog input (terminals 1, 2 and 4)
Main speed set frequency [Hz]
=
Initial value
(50% to 150%)
Voltage across terminals 2-5
75
50
37,5
25
12,5
0
×
Fig. 6-183:
Override
0
2,5
Terminal 1 input voltage [V]
Compensation amount [%]
--------------------------------------------------------------------- -
100 [%]
Terminal 2: 5V DC
(150%)
Terminal 2: 2.5V DC
(100%)
Terminal 2: 0V DC
(50%)
5
I001189E
I001190E
6 - 379

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a740 ecFr-a700 ec

Table of Contents