Multiple Rating (Sld = Super Light Duty, Ld = Light Duty, Nd = Normal Duty, Hd = Heavy Duty) (Pr. 570) - Mitsubishi Electric FR-A700 Instruction Manual

Frequency inverter
Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

Adjust the output torque of the motor (current)
6.7.5
Multiple rating (SLD = Super Light Duty, LD = Light Duty, ND = Normal
Duty, HD = Heavy Duty) (Pr. 570)
You can use the inverter by changing the overload current rating specifications according to load
applications. Note that the control rating of each function changes.
Pr.
Initial
Name
No.
Value
Multiple rating
570
setting
This function is valid for V/f control only. This parameter can be set only when "9999" is set
in Pr. 80, Pr. 81, Pr. 453, and Pr. 454.
The initial value and setting range of the following parameters are changed by performing all
parameter clear and reset after changing this parameter setting.
Pr. No. Name
Electronic thermal
9
O/L relay
Stall prevention oper-
22
ation level
Stall prevention oper-
ation level compensa-
23
tion factor at double
speed
Second stall preven-
48
tion operation current
Current monitoring
56
reference
Reference value at
62
acceleration
Reference value at
63
deceleration
Third stall prevention
114
operation current
Stall prevention level
148
at 0V input
Stall prevention level
149
at 10V input
Output current detec-
150
tion level
Zero current detection
152
level
Tab. 6-34:
Influence of Pr. 570 on other parameters (1)
6 - 166
Setting
Description
Range
SLD
Ambient temperature 40°C,
0
Overload current rating 110% 60s, 120% 3s
(Inverse time characteristics)
LD
Ambient temperature 50°C,
1
Overload current rating 120% 60s, 150% 3s
(Inverse time characteristics)
2
ND
Ambient temperature 50°C,
2
Overload current rating 150% 60s, 200% 3s
(Inverse time characteristics)
HD
Ambient temperature 50°C,
3
Overload current rating 200% 60s, 250% 3s
(Inverse time characteristics)
SLD rated
Initial Value
current
Setting Range
0–400%
Initial Value
110 %
Setting Range
0–150%/9999
Initial Value
9999
Setting Range
0–120%
Initial Value
110%
SLD rated
Initial Value
current
Setting Range
0–120%
Initial Value
9999
Setting Range
0–120%
Initial Value
9999
Setting Range
0–120%
Initial Value
110%
Setting Range
0–120%
Initial Value
110%
Setting Range
0–120%
Initial Value
120%
Setting Range
0–120%
Initial Value
110%
Setting Range
0–120%
Initial Value
Pr. 570
0
1
LD rated
current
0–400%
120 %
0–200%/9999
9999
0–150%
120%
LD rated
current
0–150%
9999
0–150%
9999
0–150%
120%
0–150%
120%
0–150%
150%
0–150%
120%
0–150%
5%
5%
Parameters referred to
2
3
(initial value)
ND rated
HD rated
current
current
0–400%
0–400%
150 %
200 %
0–200%/9999
0–200%/9999
9999
9999
0–220%
0–280%
150%
200%
ND rated
HD rated
current
current
0–220%
0–280%
9999
9999
0–220%
0–280%
9999
9999
0–220%
0–280%
150%
200%
0–220%
0–280%
150%
200%
0–220%
0–280%
200%
250%
0–220%
0–280%
150%
200%
0–220%
0–280%
5%
5%
Parameter
Refer to
Section
Refer
to
Page
6-212
6-80,
6-155
6-155
6-155
6-330
6-208
6-208
6-155
6-155
6-155
6-312
6-312