Mitsubishi Electric FR-A700 Instruction Manual page 364

Frequency inverter
Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

Frequency setting by external terminals
Operation is performed at the frequency set in Pr. 4 when the RH signal turns on, Pr. 5 when the
RM signal turns on, and Pr. 6 when the RL signal turns on.
Frequency from speed 4 to speed 15 can be set according to the combination of the RH, RM,
RL and REX signals. Set the running frequencies in Pr. 24 to Pr. 27, Pr. 232 to Pr. 239. (In the
initial value setting, speed 4 to speed 15 are unavailable.)
RH
RM
RL
Fig. 6-65: Multi-speed selection by external terminals
Fig. 6-66: Multi-speed selection by external terminals
When "9999" is set in Pr. 232 "Multi-speed setting (speed 8)", operation is performed at
frequency set in Pr. 6 when RH, RM and RL are turned off and REX is turned on.
NOTES
In the initial setting, if two or three speeds are simultaneously selected, priority is given to
the set frequency of the lower signal. For example, when the RH and RM signals turn on, the
RM signal (Pr. 5) has a higher priority.
The RH, RM, RL signals are assigned to the terminal RH, RM, RL in the initial setting. By
setting "0 (RL)", "1 (RM)", "2 (RH)" in any of Pr. 178 to Pr. 189 "Input terminal function assig-
nment", you can assign the signals to other terminals.
For the terminal used for REX signal input, set "8" in any of Pr. 178 to Pr. 186 to assign the
function.
6 - 184
Speed 1 (high speed)
Speed 2
(middle speed)
ON
ON
Speed 9
Speed 8
RH
RM
ON
RL
ON
ON
REX
Speed 4
Speed 2
(low speed)
ON
ON
ON
Speed 10
Speed 11
Speed 12
Speed 13
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
Speed 5
Speed 6
Speed 7
ON
ON
ON
ON
ON
ON
Speed 14
Speed 15
ON
ON
ON
ON
ON
ON
ON
Parameter
t
I000004aC
I000005C

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a740 ecFr-a700 ec

Table of Contents