Function assignment of external terminals
When you refer to Fig. 6-141 and set "1" to the terminal bit (terminal where the REM signal has
been assigned) of Pr. 496 or Pr. 497, the output terminal turns on (off for sink logic). By setting
"0", the output terminal turns off (on for sink logic).
Example
When "96" (source logic) is set to Pr. 190 "RUN terminal function selection" and "1" (H01) is
set to Pr. 496, the terminal RUN turns on.
Fig. 6-141: Remote output data
As desired (always "0" when read).
Y0 to Y6 are available only when the extension output option (FR-A7AY) is fitted.
RA1 to RA3 are available only when the relay output option (FR-A7AR) is fitted.
6 - 316
Pr. 496
Pr. 497
Parameter