Parameter
NOTES
The RT(X9) signal acts as the second (third) function selection signal and makes the other
second (third) functions valid. (Refer to section 6.14.3.)
The RT signal is assigned to the RT terminal in the default setting. By setting "3" in any of
Pr. 178 to Pr. 189 "Input terminal function selection", you can assign the RT signal to the
other terminal.
Increase the setting when the distance between the inverter and motor is long or when
motor torque is insufficient in the low-speed range. If the setting is too large, an overcurrent
trip may occur.Überstromauslösung kommen.
The Pr. 0, Pr. 46, Pr. 112 settings are valid only when V/f control is selected.
When using the inverter dedicated motor (constant torque motor) with the 00170 or 00250,
set the torque boost value to 2%. If the initial set Pr. 71 value is changed to the setting for
use with a constant-torque motor, the Pr. 0 setting changes to the corresponding value in
above.
Changing the terminal assignment using Pr. 178 to Pr. 189 "Input terminal function selec-
tion" may affect the other functions. Please make setting after confirming the function of
each terminal.
FR-A700 EC
Adjust the output torque of the motor (current)
6 - 149