Parameter
Setting torque bias amount with terminal 1 (Pr. 840 = 3)
● C16 "Terminal 1 bias command (torque/magnetic flux)", C17 "Terminal 1 bias (torque/
magnetic flux)", C18 "Terminal 1 gain command (torque/magnetic flux)", C19 "Terminal 1
gain (torque/magnetic flux)", and Pr. 846 "Torque bias balance compensation" can be set
automatically according to the load.
● When torque command is set from terminal 1, set "6" in Pr. 868 "Terminal 1 function
assignment".
● Setting C16, C17 (Pr. 919) , C18, C19 (Pr. 920):
● Setting Pr. 846:
NOTE
When starting torque bias operation after completion of automatic setting, set "1 or 2" in
Pr. 840.
FR-A700 EC
Speed control by real sensorless vector control, vector control
Operation without
a load
Press the SET key.
(setting C18, C19
(Pr. 920) is
completed))
Operation with
a balanced load
Read C16, C17
(Pr. 919) when
speed is stable
Read C18, C19
(Pr. 920) when speed
is stable
Read 846
Press the SET key.
(setting C16, C17
(Pr. 919) is completed)
Operation with
a maximum load
Press the SET key.
Torque balance
compensation under
power driving is
completed.
6 - 105