Mitsubishi Electric FR-A700 Instruction Manual page 409

Frequency inverter
Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

Parameter
Display during tuning
Monitor is displayed on the operation panel and parameter unit (FR-PU04/FR-PU07) during tun-
ing as shown below..
Pr. 96
Setting
Tuning in
progress
Normal end
Error end
(when inverter
protective func-
tion operation is
activated)
Tab. 6-50: Display during tuning (monitor display)
Offline Auto Tuning Setting
Non-rotation mode (Pr. 96 = 1)
Rotation mode (Pr. 96 = 101)
Tab. 6-51: Offline auto tuning time (when the initial value is set)
Return to normal operation
When offline auto tuning ends, press the STOP/RESET key of the operation panel during PU
operation. For external operation, turn off the start signal (STF signal or STR signal) once. This
operation resets the offline auto tuning and the PU's monitor display returns to the normal indi-
cation. (Without this operation, next operation cannot be started.)
NOTE
Do not change the Pr. 96 setting after completion of tuning (3 or 103). If the Pr. 96 setting is
changed, tuning data is made invalid and tuning must be performed again.
FR-A700 EC
Parameter Unit
(FR-PU04/FR-PU07) Display
1
101
Selection and protection of a motor
Operation Panel (FR-DU07) Indication
1
blinkt
Time
Approximately 25 to 120s
(Tuning time differs according to the inverter capacity
and motor type.)
Approximately 40s
(Offline auto tuning time varies with the acceleration and
deceleration time settings as indicated below.
Offline auto tuning time = acceleration time + decelera-
tion time + approx. 30s)
101
blinkt
6 - 229