Torque control by real sensorless vector control, vector control
Control block diagram
Analog input
Parameter
(Pr. 805, Pr. 806)
16 bit digital input
(FR-A7AX)
Fig. 6-26: Block diagram
Torque command (Pr. 804 = 0 (initial value)) by analog input (terminal 1)
● Torque command is given by voltage (current) input to terminal 1.
● When torque command is input from terminal 1, set "4 or 3" in Pr. 868 "Terminal 1 function
assignment".
● Torque command by analog input can be calibrated using calibration parameter C16
(Pr. 919) to C19 (Pr. 920). (Refer to section 6.20.6.)
−100%
(−10V)
6 - 114
Pr. 804
Torque command source selectiont
Speed limit input
Torque command
150%
−150%
Speed estimated value < Speed limit value
Drehzahlregelung
(P-Anteil)
Speed estimated value ≥ Speed limit value
Encoder feedback in vector control
Fig. 6-27:
Torque command by terminal 1
100%
Terminal 1
(+10V)
analog input
Parameter
Torque
control
Encoder
Speed estimator in
sensorless vector
control
I001523E
M
3~
I001524E