4.2.28 Retry function (Pr. 65, Pr. 67 to Pr. 69)

Pr. 65 "retry selection"
Pr. 67 "number of retries at alarm occurrence"
Pr. 68 "retry waiting time"
Pr. 69 "retry count display erasure"
When an alarm occurs, the retry function causes the inverter to automatically reset itself to make a restart and
continue operation. You can select whether retry is made or not, alarms reset for retry, number of retries made,
and waiting time.
Parameter
Factory
Number
Setting
65
0
67
0
68
1 s
69
0
<Setting>
Use Pr. 65 to select alarms to be reset for retry.
Errors Reset for Retry
Display
E.OC1
E.OC2
E.OC3
E.OV1
E.OV2
E.OV3
E.THM
E.THT
E.IPF
E.UVT
E.FIN
E. GF
E. LF
E.OHT
E.OLT
E.OPT
E.OP1
E.OP2
E.OP3
E. PE
E.PUE
E.RET
E.CPU
E.E6
E.E7
E.P24
E.CTE
E.15
Note:
indicates the errors selected for retry.
Setting Range
0 to 5
0 to 10, 101 to 110
0 to 10 s
0
Setting
0
1
2
3
90
4
5
PARAMETERS
4