Common specifications
FR-A 740
Operating status
Output signals
When using the
FR-A7AY, FR-A7AR
options
Pulse/analog output
Operating status
Control unit display
(FR-DU07/FR-PU07/
FR-PU04)
Alarm definition
Interactive guidance
Protective functions
Ambient temperature
Storage temperature
Ambient humidity
Ambience conditions
Altitude
Vibration resistance
Tab. A-3: Common specifications
Available only when the option FR-A7AP is mounted.
The product may only be exposed to the full extremes of this temperature range for short
periods (e.g. during transportation).
2.9 m/s² or less for the 04320 or more.
A - 6
You can select any signals using Pr. 190 to Pr. 196 (output terminal function selection) from
among inverter running, up-to-frequency, instantaneous power failure/undervoltage, overload
warning, output frequency (speed) detection, second output frequency (speed) detection, third
output frequency (speed) detection, regenerative brake prealarm, electronic thermal relay function
pre-alarm, PU operation mode, inverter operation ready, output current detection, zero current
detection, PID lower limit, PID upper limit, PID forward rotation reverse rotation output, electronic
bypass MC1, electronic bypass MC2, electronic bypass MC3, orientation completion
opening request, fan fault output, heatsink overheat pre-alarm , inverter running/start command
on, deceleration at an instantaneous power failure, PID control activated, during retry, PID output
interruption, life alarm, alarm output 1, 2, 3 (power-off signal), power savings average value
update timing, current average monitor, maintenance timer alarm, remote output, forward rota-
tion output , reverse rotation output , low speed output, torque detection, regenerative status
output , start-time tuning completion, in-position completion , minor failure output and alarm
output. Open collector output (5 points), relay output (2 points) and alarm code of the inverter
can be output (4 bit) from the open collector
You can select any seven signals using Pr. 313 to Pr. 319 (extension output terminal function
selection) from among control circuit capacitor life, main circuit capacitor life,
cooling fan life, inrush current limit circuit life
(Only positive logic can be set for extension terminals of the FR-A7AR)
You can select any signals using Pr. 54 "FM terminal function selection (pulse train output)" and
Pr. 158 "AM terminal function selection (analog output)" from among output frequency, motor
current (steady or peak value), output voltage, frequency setting, operation speed, motor torque,
converter output voltage (steady or peak value), electronic thermal relay function load factor,
input power, output power, load meter, motor excitation current, reference voltage output, motor
load factor, power saving effect, regenerative brake duty ,PID set point, PID measured value, PLC
function output, motor output, torque command, torque current command, and torque monitor.
Output frequency, motor current (steady or peak value), output voltage, frequency setting, run-
ning speed,motor torque, overload, converter output voltage (steady or peak value),
electronic thermal relay function load factor, input power, output power, load meter,
motor excitation current, cumlative energization time, actual operation time, motor load factor,
cumulative power, energy saving effect, cumulative saving power, regenerative brake duty,
PID set point, PID measured value, PID deviation, inverter I/O terminal monitor, input terminal
option monitor (FR-DU07 only), output terminal option monitor (FR-DU07 only), option fitting
status (FR-PU07/FR-PU04 only), terminal assignment status (FR-PU07/FR-PU04 only),
torque command, torque current command, feed back pulse
Alarm definition is displayed when the protective function is activated,
the output voltage/current/frequency/cumulative energizing time right before the protection
function was activated and the past 8 alarm definitions are stored.
Operation guide/trouble shooting with a help function (FR-PU07/FR-PU04 only)
Overcurrent during acceleration, overcurrent during constant speed, overcurrent during
deceleration, overvoltage during acceleration, overvoltage during constant speed, overvoltage
during deceleration, inverter protection thermal operation, motor protection thermal operation,
heatsink overheat, instantaneous power failure occurrence, undervoltage, input phase failure,
motor overload, output side earth (ground) fault overcurrent, output short circuit, main circuit ele-
ment overheat, output phase failure, external thermal relay operation, PTC thermistor operation,
option alarm, parameter error, PU disconnection, retry count excess, CPU alarm, operation panel
power supply short circuit, 24VDC power output short circuit, output current detection value
excess, inrush current limit circuit alarm, communication alarm (inverter), USB error, opposite
rotation deceleration error, analog input error, fan fault, overcurrent stall prevention, overvoltage
stall prevention, regenerative brake prealarm, electronic thermal relay function prealarm, PU stop,
maintenance timer alarm (FR-DU07 only), brake transistor alarm, parameter write error, copy
operation error, operation panel lock, parameter copy alarm, speed limit indication, encoder no-
signal
, speed deviation large
For selection of the load characteristics with a 120% overload rating the max. temperature is 40°C
Max. 90 % RH (non-condensing)
For indoor use only, avoid environments containing corrosive gases, install in a dust-free location.
Maximum 1000m above sea level for standard operation.
After that derate by 3% for every extra 500 m up to 2500 m (92%)
5.9 m/s² or less (JIS 60068-2-6)
Specification
, overspeed
, position error large
-10 °C to +50 °C (non-freezing)
-20 °C to +65 °C
Appendix
, brake
, motor output
, encoder phase error