Parameter
Pulse train form type selection (Pr. 428, NP signal)
● Set "2" (conditional pulse train position command) in Pr. 419.
● Set "68" in Pr. 178 to Pr. 189 "Input terminal function selection" to assign conditional position
pulse train sign (NP).
● Select command pulse train using Pr. 428.
Pr. 428
Tab. 6-24: Setting of parameter 428
● Select vector control, then select position control.
NOTE
When Pr. 419 "Position command source selection" = 2 (conditional pulse train position
command), JOG terminal serves as conditional position pulse train input terminal regardless
of the Pr. 291 "Pulse train input selection" setting.
Selection of clear signal (Pr. 429, CLR signal)
● Use this function to zero the droop pulse for home position operation, etc.
● When "0" is set in Pr. 429, the deviation counter is cleared at the edge of turning on of the
clear signal (CLR). In addition, the CLR signal turns on in synchronization with zero pulse
signal of the encoder at home position operation, etc., deviation counter is cleared.
● For the terminal used for CLR signal, set "69" in any of Pr. 178 to Pr. 189 "Input terminal
function selection" to assign the function.
Deviation counter
Fig. 6-42: Clear the droop pulse
FR-A700 EC
Command Pulse Train Type
0–2
Sink logic
3–5
Sink logic
Pr. 429 = 0
image
CLR
Counter clear at the edge of
turning on of the signal
At Forward Rotation At Reverse Rotation
Pulse train + sign
IPulse train + sign
Deviation counter
image
ON
CLR
Position control by vector control
JOG
NP
L
H
JOG
NP
H
L
Pr. 429 = 1 (initial value)
ON
Counter clear while ON
I001541E
6 - 135