Simple mode parameter list
Setting
Set "1" or "101" in Pr. 96 "Auto tuning setting/status".
● When the setting is "1"
Tuning is performed without motor running. It takes approximately 25 to 120s* until tuning
is completed. (Excitation noise is produced during tuning.)
(* Tuning time differs according to the inverter capacity and motor type.)
● When the setting is "101"
Tuning is performed without motor running. It takes approximately 40s until tuning is
completed. The motor runs at nearly its rated frequency.
Set the rated voltage of motor in Pr. 83 "Motor rated voltage" and rated frequency of motor in
Pr. 84 "Rated motor frequency".
Set Pr. 71 "Applied motor" according to the motor used.
Motor
Mitsubishi standard motor,
Mitsubishi high efficiency motor
Mitsubishi constant-torque motor
Vector control dediated motor
Other manufacturer's standard motor —
Other manufacturer's constant-
torque motor
Tab. 5-3: Motor selection
For other settings of Pr. 71 , refer to section 6.12.2.
5 - 26
SF-JR, SF-TH
SF-JR 4P-1.5kW or less
SF-HR
Others
SF-JRCA 4P, SF-TH (constant-
torque)
SF-HRCA 4P
Others (SF-JRC, etc.)
SF-V5RU, SF-THY
—
Basic settings
Pr. 71
3
23
43
3
13
53
13
33
3
13