Mitsubishi Electric FR-A700 Instruction Manual page 193

Frequency inverter
Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

Parameter
Parameter
Func-
Name
tion
Watt-hour meter clear
170
Operation hour meter
171
clear
Monitor decimal digits
268
selection
Energizing time
563
carrying-over times
Operating time
564
carrying-over times
Cumulative power
monitor digit shifted
891
times
Frequency monitoring
55
reference
Current monitoring
56
reference
Torque monitoring
866
reference
AM output filter
867
Current output filter
869
Tab. 6-1:
Parameter overview (13)
FR-A700 EC
Incre-
Initial
Setting
ments
Value
Range
0
10
1
9999
9999
1
9999
0/9999
0
1
9999
1
9999
1
0
0–65535
1
0
0–65535
0–4
1
9999
9999
0.01 Hz
50Hz
0–400Hz
Rated
0.01/
inverter
0–500/
0.1 A *
output
0–3600A *
current
0.1%
150%
0–400%
0.01s
0.01s
0–5s
0.01s
0.02s
0–5s
Description
Set "0" to clear the watt-hour meter
monitor.
Set the maximum value when
monitoring from communication
to 0 to 9999kWh.
Set the maximum value when
monitoring from communication
to 0 to 65535kWh.
Set "0" in the parameter to clear
the watt hour monitor.
Setting "9999" has no effect.
Displays the monitor as integral
value.
Displays the monitor in incre-
ments of 0.1.
No fixed decimal position
The numbers of cumulative ener-
gizing time monitor exceeded
65535h is displayed.
Reading only
The numbers of operation time
monitor exceeded 65535h is dis-
played.
Reading only
Set the number of times to shift
the cumulative power monitor
digit.
Clamp the monitor value at maxi-
mum.
No shift
Clear the monitor value when it
exceeds the maximum value.
Set the full-scale value to output
the output frequency monitor
value to terminal CA and AM.
Set the full-scale value to output
the output current monitor value
to terminal CA and AM.
* The setting depends on the
inverter capacity:
(01800 or less/02160 or more)
Set the full-scale value to output
the torque monitor value to termi-
nal CA and AM.
Set the output filter of terminal AM.
Adjust response level of current
output.
Parameter overview
All
Para-
Para-
para-
meter
meter
meter
copy
clear
Refer
clear
to
page
✔: enabled
—: disabled
6-321
6-330
6 - 13

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a740 ecFr-a700 ec

Table of Contents