Mitsubishi Electric FR-A700 Instruction Manual page 518

Frequency inverter
Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

Operation selection at power failure
Pr.
Name
No.
57
Restart coasting time
58
Restart cushion time
162
Automatic restart after
instantaneous power
failure selection
First cushion time for
163
restart
First cushion voltage
164
for restart
Stall prevention opera-
165
tion level for restart
Rotation direction
299
detection selection at
restarting
Acceleration time at a
611
restart
When Pr. 570 Multiple rating setting ≠ "2", performing all parameter clear and inverter reset
changes the initial value and setting range.
6 - 338
Initial
Setting
Value
Range
0
01800
or
0.1–5s
9999
less
02160
or
0.1–30s
more
9999
1s
0–60s
0
1
2
0
10
11
12
0s
0–20s
0%
0–100%
150%
0–220%
0
1
9999
9999
01800
or
5s
less
0–3600s, 9999
02160
or
15s
more
Description
00052 or less .................... 0.5s
00083–00250....................... 1s
00310, 0,1800...................... 3s
02160 or more ..................... 5s
Set the waiting time for inverter-
triggered restart after an instanta-
neous power failure.
No restart
Set a voltage starting time at
restart.
With frequency search
Without frequency search
(reduced voltage system)
Encoder detection frequency
search
Frequency search at every start
Reduced voltage system at every
start
Encoder detection frequency
search at every start
Set a voltage starting time at
restart.
Consider using these parameters
according to the load (inertia
moment, torque) magnitude.
Consider the rated inverter cur-
rent according to the overload
capacity as 100% and set the stall
prevention operation level during
restart operation.
Without rotation direction
detection
With rotation direction detection
When Pr. 78 = "0", the rotation
direction is detected.
When Pr. 78 = "1","2", the rotation
direction is not detected.
Set the acceleration time to reach
the set frequency at a restart.
Acceleration time for restart is the
normal acceleration time (e.g.
Pr. 7) when "9999" is set.
Parameter
Parameters referred to
7
Acceleration time
21
Acceleration/
deceleration time
increments
13
Starting frequency
65
Retry selection
67–69
Retry function
178–189
Input terminal
function selection
Refer to
Section
6.11.1
6.11.1
6.11.2
6.17.1
6.17.1
6.14.1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a740 ecFr-a700 ec

Table of Contents