Parameter
● Run command
Item
Run
command
Run
command
(extended)
Tab. 6-144: Run commands
The signal within parentheses is the initial setting. The description changes depending on
the setting of Pr. 180 to Pr. 184 and Pr. 187 "Input terminal function selection". (Refer to
section 6.14.1.)
The signal within parentheses is the initial setting. Since jog operation/selection of automatic
restart after instantaneous power failure/start self-holding/reset cannot be controlled by the
network, bit 8 to bit 11 are invalid in the initial status. When using bit 8 to bit 11, change the
signals with Pr. 185, Pr. 186, Pr. 188, Pr. 189 "Input terminal function selection" (section
6.14.1). (Reset can be executed with the instruction code HFD.)
FR-A700 EC
Instruction
Bits
Description
Code
b0: AU (current input
selection)
b1: Forward rotation start
b2: Reverse rotation start
b3: RL (low speed)
HFA
8
b4: RM (middle speed)
b5: RH (high speed)
b6: RT (second function
selection)
b7: MRS (output stop)
b0: AU (current input
selection)
b1: Forward rotation start
b2: Reverse rotation start
b3: RL (low speed)
b4: RM (middle speed)
b5: RH (high speed)
b6: RT (second function
selection)
b7: MRS (output stop)
HF9
16
b8: JOG (Jog operation)
b9: CS (automatic restart
after instantaneous
power failure)
b10: STOP (start self-
holding)
b11: RES (reset)
b12: —
b13: —
b14: —
b15: —
Communication operation and setting
Example
Example 1: H02 (Forward rotation)
Example 2: H00 (Stop)
Example 1: H0002 (Forward rotation)
Example 2: H0800 low speed operation
(When Pr. 189 "RES terminal function selection" is set
to "0")
6 - 465