Mitsubishi Electric FR-A700 Instruction Manual page 481

Frequency inverter
Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

Parameter
Setting
Terminal Function
Source
Sink
Logic
Logic
64
164
Y64
70
170
SLEEP
84
184
RDY
85
185
Y85
90
190
Y90
91
191
Y91
92
192
Y92
93
193
Y93
94
194
ALM2
95
195
Y95
96
196
REM
Tab. 6-86:
Output terminal function assignment (4)
FR-A700 EC
During retry
PID output interruption
Position control preparation
ready
DC feeding
Life alarm
Alarm output 3 (power-off signal)
Energy saving average value
updated timing
Current average value monitor
signal
Alarm output 2
Maintenance timer signal
Remote output
Function assignment of external terminals
Operation
Output during retry
processing.
Output when the PID output
interruption function is
executed.
Signal is output when the
servo is on (LX-ON) and
ready to operate.
This signal turns on during
power failure or under voltage
of AC power.
Output when any of the con-
trol circuit capacitor, main cir-
cuit capacitor and inrush
current limit circuit or the
cooling fan approaches the
end of its service life.
Output when an error occurs
due to the circuit failure or
connection alarm of the
inverter.
Turned on and off alternately
every time the power saving
average value is updated
when the power saving moni-
tor is used. Cannot be set to
Pr. 195 and Pr. 196 (relay out-
put terminal).
Average current value and
maintenance timer value are
output as pulses. Cannot be
set to Pr. 195 and Pr. 196
(relay output terminal).
Output when the inverter's
protective function is acti-
vated to stop the output
(major fault). Continue output-
ting the signal during inverter
reset and stop outputting after
reset is cancelled.
Output when Pr. 503 rises to
or above the Pr. 504 setting.
Output to the terminal when a
value is set to the parameter.
Related Parame-
Refer to
ters
Page
Pr. 65–Pr. 69
6-351
Pr. 127–Pr. 134,
6-488
Pr. 575–Pr. 577
Pr. 419,
6-134
Pr. 428–Pr. 430
Pr. 30, Pr. 70
6-247
Pr. 255–Pr. 259
6-527
6-308
Pr. 52, Pr. 54,
Pr. 158,
6-360
Pr. 891–Pr. 899
Pr. 555–Pr. 557
6-532
6-308
Pr. 503, Pr. 504
6-531
Pr. 495–Pr. 497
6-315
6 - 301

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a740 ecFr-a700 ec

Table of Contents