Basic Settings; Simple Mode Parameter List - Mitsubishi Electric FR-A700 Instruction Manual

Frequency inverter
Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

Basic settings

5
Basic settings
5.1

Simple mode parameter list

For simple variable-speed operation of the inverter, the initial setting of the parameters may be
used as they are. Set the necessary parameters to meet the load and operational specifications.
Parameter setting, change and check can be made from the operation panel (FR-DU07). For de-
tails of parameters, refer to chapter 6.
NOTE
Simple mode and extended mode parameters are displayed by the initial setting of Pr. 160
"User group read selection". Set Pr. 160 "
section 6.21.4.)
(Initial value)
Tab. 5-1: Setting of parameter 160
Pr.
Name
0
Torque boost
1
Maximum frequency
2
Minimum frequency
3
Base frequency
Multi-speed setting
4
(high speed)
Multi-speed setting
5
(middle speed)
Multi-speed setting
6
(low speed)
Tab. 5-2: Simple mode parameters (1)
FR-A700 EC
Pr. 160
Description
9999
Only the simple mode parameters can be displayed.
0
Simple mode and extended mode parameters can be displayed.
1
Only parameters registered in the user group can be displayed.
Incre-
ments
0.1%
0.01Hz
0.01Hz
0.01Hz
0.01Hz
0.01Hz
0.01Hz
User group read selection" as required.
Initial
Range
Description
Value
Set to increase a starting torque or
when the motor with a load will not
rotate, resulting in an alarm (OL)
and a trip (OC1).
6/4/3/2/1
0–30%
Set when the maximum output fre-
quency need to be limited.
120/
0–120Hz
60Hz
Set when the minimum output fre-
0Hz
0–120Hz
quency need to be limited.
50Hz
0–400Hz
Check the motor rating plate.
50Hz
0–400Hz
Set when changing the preset
30Hz
0–400Hz
speed in the parameter with a
terminal.
10Hz
0–400Hz
Simple mode parameter list
Initial values differ according to
the inverter capacity.
(00023, 00038/00052 to 00126/
00170, 00250/00310 to 01800/
021600 or more)
Initial values differ according to
the inverter capacity.
(01800 or less/02160 or more)
(Refer to
Refer
to
5-6
5-8
5-5
5-51
5 - 1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a740 ecFr-a700 ec