Selection of operation mode and operation location
PU operation mode (Pr. 79 = 1)
Select the PU operation mode when performing operation by only the key operation of the oper-
ation panel (FR-DU07) or parameter unit (FR-PU04/FR-PU07). Also select the PU operation
mode when making communication using the PU connector.
When "1" is selected for Pr. 79, the inverter enters the PU operation mode at power on. You can-
not change to the other operation mode.
The setting dial of the operation panel can be used for setting like a volume. (Pr. 161 "Frequency
setting/key lock operation selection", refer to section 6.26.2.)
When PU operation mode is selected, the PU operation mode signal (PU) can be output. For the
terminal used for the PU signal output, assign the function by setting "10 (source logic) or 110
(sink logic)" in any of Pr. 190 to Pr. 196 "output terminal function selection".
PU/external combined operation mode 1 (Pr. 79 = 3)
Select the PU/external combined operation mode 1 when making frequency setting from the
operation panel FR-DU07 (digital dial) or parameter unit (FR-PU04/FR-PU07) and inputting the
start command with the external start switch.
Select "3" for Pr. 79. You cannot change to the other operation mode by using the PU/EXT-key.
When a frequency is input from the external signal by multi-speed setting, it has a higher priority
than the frequency setting of the PU. When AU is on, the terminal 4 is used.
Power supply
Forward
rotation start
Reverse
rotation start
6 - 420
Inverter
Power
supply
Inverter
Set frequency
Fig. 6-206:
PU operation mode
Motor
Fig. 6-207:
Combined operation mode 1
Motor
Parameter
I001206E
I001207E