Parameter
Set the minimum frequency
Use Pr. 2 "Minimum frequency" to set the lower limit of the output frequency. The output fre-
quency is clamped by the Pr. 2 setting even the set frequency is lower than the Pr. 2 setting (The
frequency will not decrease to the Pr. 2 setting.)
NOTES
When Pr. 15 "Jog frequency" is equal to or less than Pr. 2, the Pr. 15 setting has precedence
over the Pr. 2 setting.
When stall prevention is activated to decrease the output frequency, the output frequency
may drop to Pr. 2 or below.
b
CAUTION:
If the Pr. 2 setting is higher than the Pr. 13 "Starting frequency" value, note that the
motor will run at the set frequency according to the acceleration time setting by merely
switching the start signal on, without entry of the command frequency.
FR-A700 EC
Limit the output frequency
6 - 169