Mitsubishi Electric FR-A700 Instruction Manual page 403

Frequency inverter
Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

Parameter
Pr.
Name
No.
90
Motor constant (R1)
91
Motor constant (R2)
92
Motor constant (L1)
93
Motor constant (L2)
94
Motor constant (X)
Auto tuning setting/
96
status
Second applied
450
motor
Second motor
453
capacity
Number of second
454
motor poles
Second motor exci-
455
tation current
FR-A700 EC
Initial
Setting Range
Value
01800
0–50Ω/
or
9999
less
9999
02160
0–400mΩ/
or
9999
more
01800
0–50Ω/
or
9999
less
9999
02160
0–400mΩ/
or
9999
more
01800
0–50Ω/
or
(0–1000 mH)/
less
9999
9999
02160
0–3600 mΩ/
or
(0–400 mH)/
more
9999
0–50 Ω/
01800
or
(0–1000 mH)/
less
9999
9999
02160
0–3600mΩ/
or
(0–400 mH)/
more
9999
01800
0–500Ω/
or
(0–100 %)/
less
9999
9999
02160
0–100Ω/
or
(0–100 %)/
more
9999
0
0
1
101
0 to 8/13 to18/20/
23/24/30/33/34/40/
9999
43/44/50/53/54
9999
01800
0.4 to
or
55kW
less
02160
9999
0 to
or
3600kW
more
9999
2/4/6/8/10
9999
9999
01800
or
0 to 500A
less
02160
or
0 to 3600A
9999
more
9999
Description
Tuning data (The value measured
by offline auto tuning is automati-
cally set.)
9999: Use the Mitsubishi motor
(SF-JR,SF-HR, SF-JRCA, SF-
HRCA) constants
Offline auto tuning is not per-
formed
Offline auto tuning is performed
without motor running
Offline auto tuning is performed
with motor running
Set when using the second motor.
(same specifications as Pr. 71)
Second motor is invalid
Set the capacity of the second
motor.
V/f control
Set the number of poles of the
second motor.
V/f control
Tuning data of the second motor
(The value measured by offline
auto tuning is automatically set.)
Use the Mitsubishi motor (SF-JR,
SFHR, SF-JRCA, SF-HRCA) con-
stants
Selection and protection of a motor
Parameters referred to
See previous page
Refer to
Section
6 - 223

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a740 ecFr-a700 ec

Table of Contents