Parameter
Switching of operation mode by external terminal (X65, X66)
When Pr. 79 = any of "0, 2, 6, 7", the operation mode switching signals (X65, X66) can be used
to change the PU or external operation mode to network operation mode during a stop (during
a motor stop or start command off). (Pr. 79 = 6 switch-over mode can be changed during oper-
ation)
When switching between the network operation mode and PU operation mode:
Set Pr. 79 to "0" (initial value), "6" or "7". (At the Pr. 79 setting of "7", the operation mode
can be switched when the X12 (MRS) signal turns on.)
Set "10" or "12" in Pr. 340 "Communication start-up mode selection".
Set "65" to any of Pr. 178 to Pr. 189 to assign the PU-NET operation switching signal (X65)
to the external terminal.
The operation mode changes to PU operation mode when the X65 signal turns on, or to
network operation mode when the X65 signal turns off.
Pr. 340
10 / 12
Tab. 6-122: Operation mode switching by signal X65
NET operation mode when the X66 signal is on.
PU operation mode when the X16 signal is off. PU operation mode also when Pr. 550 "NET
mode operation command source selection" = 1 (communication option control source) and
the communication option is not fitted.
External operation mode when the X16 signal is on.
FR-A700 EC
Pr. 79
ON (PU)
0
(initial setting)
operation mode
1
2
3 / 4
External/PU combined operation mode
6
operation mode
X12 (MRS) ON
operation mode
7
X12 (MRS) OFF
Selection of operation mode and operation location
X65 Signal State
OFF (NET)
PU
PU
operation mode
PU operation mode
NET operation mode
PU
NET
operation mode
PU
NET
operation mode
External operation mode
Remarks
Cannot be switched to external
operation mode
Fixed to PU operation mode
Fixed to NET operation mode
External/PU combined mode fixed
Operation mode can be switched with
operation continued
Cannot be switched to external
operation mode
Output stop in external operation mode
Forcibly switched to external operation
mode
6 - 425