Simple mode parameter list
Pr.
Name
7
Acceleration time
8
Deceleration time
Electronic thermal O/L
9
relay
Operation mode
79
selection
Terminal 2 frequency
125
setting gain frequency
Terminal 4 frequency
126
setting gain frequency
User group read
160
selection
Tab. 5-2: Simple mode parameters (2)
5 - 2
Incre-
Initial
Range
ments
value
0.1s
5/15s
0–3600s
0.1s
10/30s
0–3600s
Rated
0.01/
inverter
0–500/
0.1A
output
0–3600A
current
1
0
0/1/2/3/4/6/7
0.01Hz
50Hz
0–400Hz
0.01Hz
50Hz
0–400Hz
1
9999
0/1/9999
Basic settings
Description
Acceleration/deceleration time
can be set.
Initial values differ according to
the inverter capacity.
(00250 or less/00310 or more)
Protect the motor from overheat
by the inverter.
Set the rated motor current.
The increments and setting
range differ according to
the inverter capacity.
(01800 or less/02160 or more)
Select the start command location
and frequency command location.
Frequency for the maximum value
of the potentiometer (5V initial
value) can be changed.
Frequency for the maximum cur-
rent input (20mA initial value) can
be changed.
Make extended parameters valid
Refer
to
5-10
5-3
5-12
5-57
5-60
6-412