Communication operation and setting
6.23.2

RS-485 terminals

Fig. 6-214: RS-485 terminals layout
Tab. 6-131: RS-485 terminal description
6 - 440
Name
Description
RDA1 (RXD1+)
Inverter receive+
RDB1 (RXD1−)
Inverter receive−
RDA2 (RXD2+)
Inverter receive+ (for connection of further stations)
RDB2 (RXD2−)
Inverter receive− (for connection of further stations)
SDA1 (TXD1+)
Inverter send+
SDB1 (TXD1−)
Inverter send−
SDA2 (TXD2+)
Inverter send+ (for connection of further stations)
SDB2 (TXD2−)
Inverter send− (for connection of further stations)
PS5 (VCC)
5V power supply, permissible load current: 100mA
SG (GND)
Earth (connected to terminal SD)
Terminating resistor switch
Factory-set to "OPEN".
Set only the terminating resistor switch of the remotest
inverter to the "100 Ω" position.
Parameter
I001033E