Parameter
NOTES
When Pr. 29 "Acceleration/deceleration pattern selection" = "1" (S-pattern acceleration/
deceleration A), the acceleration/deceleration time is the period of time required to reach
Pr. 3 "Base frequency".
The Pr. 15 setting should be equal to or higher than the Pr. 13 "Starting frequency setting".
The JOG signal can be assigned to the input terminal using any of Pr. 178 to Pr. 189 "Input
terminal function selection". When terminal assignment is changed, the other functions may
be affected. Please make setting after confirming the function of each terminal.
During jog operation, the second acceleration/deceleration via the RT signal cannot be
selected. (The other second functions are valid (refer to section 6.14.3)).
When Pr. 79 "Operation mode selection" = 4, push the FWD/REV key of the PU (FR-DU07/
FR-PU04/FR-PU07) to make a start or push the STOP/RESET key to make a stop.
This function is invalid when Pr. 79 = 3 or 6.
Jog operation is invalid under position control.
FR-A700 EC
Frequency setting by external terminals
6 - 189