Jog Operation (Pr. 15, Pr. 16) - Mitsubishi Electric FR-A700 Instruction Manual

Frequency inverter
Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

Frequency setting by external terminals
6.10.2

Jog operation (Pr. 15, Pr. 16)

You can set the frequency and acceleration/deceleration time for jog operation. Jog operation
can be performed from either the outside or PU.
Can be used for conveyor positioning, test operation, etc.
Pr.
Name
No.
15
Jog frequency
Jog acceleration/
16
deceleration time
The above parameters are displayed as simple mode parameters only when the parameter unit
(FR-PU04) is connected. When the operation panel (FR-DU07) is connected, the above param-
eters can be set only when Pr. 160 "User group read selection" = 0.
Jog operation from outside
When the jog signal is on, a start and stop can be made by the start signal (STF, STR). (The jog
signal is assigned to the terminal JOG in the initial setting.)
Forward rotation start
Reverse rotation start
Fig. 6-68: Connection diagram for external jog operation
6 - 186
Initial
Setting Range
Description
Value
5Hz
0–400Hz
Set the frequency for jog operation.
Acceleration/deceleration time for jog
operation.
This setting is related to to the reference
frequency set in Pr. 20 and the increments
set in Pr. 21.
Pr. 21 = 0 (Initial setting)
0.5s
0–3600/360s
Setting range: 0–3600s
Inrements: 0.1s
Pr. 21 = 1
Setting range: 0–360 s
Inrements: 0.01s
The acceleration and deceleration times
cannot be set separately.
Power
supply
Jog operation
Parameters referred to
13
29
20
21
79
178–189
Inverter
Motor
Parameter
Refer to
Section
Starting frequency
6.11.2
Acceleration/decel-
6.11.3
eration pattern
selection
Acceleration/decel-
6.11.1
eration reference
frequency
Acceleration/
6.11.1
deceleration time
increments
Operation mode
6.22.1
selection
Input terminal
6.14.1
function selection
I001128E