Wiring
3.6

RS-485 terminal block

Specification
Conforming standard
Transmission format
Communication speed
Overall lenght
Connection cable
Tab. 3-10: Specifications of the RS-485 terminal block
Fig. 3-23: RS-485 terminal block
FR-A700 EC
Description
EIA-485 (RS-485)
Multidrop link
Max. 38400bps
500m
Twisted pair cable (4 pairs)
Terminating resistor switch
Factory-set to "OPEN".
Set only the terminating resistor switch of the first and the
remotest inverter to the "100Ω" position.
RS-485 terminal block
I001033E