Motor brake and stop operation
DC feeding mode 1 (Pr. 30 = 10 or 11)
● Setting "10, 11" in Pr. 30 enables DC power supply operation.
● Leave the AC power supply connection terminal R/L1, S/L2, and T/L3 open and connect the
DC power supply to terminal P/+ and N/-. Also, remove jumpers across terminal R/L1-R1/
L11 and S/L2-S1/L21, and connect terminals R1/L11 and S1/L21 to terminal P/+ and N/-.
The diagram below is a connection example.
Abb. 6-99: Connection example for DC feeding mode 1
6 - 250
DC power
Forward rotation start
Reverse rotation start
Frequency command
Frequency setting
potentiometer
1 kΩ, 1/2 W,
Inverter
Inrush
current limit
circuit
Parameter
M
3~
I001561E