3. Troubleshooting
Motor Does Not Run
When the motor does not run, refer to P.2-64, "Display of Factor of No-Motor Running" of Preparation
as well.
Classification
Wiring
Speed command
is invalid
(Velocity)
Speed zero
clamp input
(ZEROSPD) of
Connecter X4 is
open.
(Velocity/Torque)
Torque command
is invalid (Torque)
Velocity control is
invalid (Torque)
Installation
Main power is
shut off.
The motor shaft
drags, the motor
does not run.
Related page
• P.4-24... "Details of parameter"
Causes
Check that the velocity
command input method
(external analog
command/internal
velocity command) is
correct.
In the front panel
monitor mode, is the Pin
No. corresponding to
ZEROSPD in " A " state?
Check that the torque
command input method
(SPR/TRQR input,
P-ATL/TRQR input) is
correct.
Check that the velocity
limit input method
(parameter velocity, SPR/
TRQR/SPL input) is
correct.
In the front panel monitor
mode, is the Pin No.
corresponding to S-RDY
in " - " state?
1)Check that you can
turn the motor shaft,
after turning off the
power and separate it
from the machine.
2)Check that you can
turn the motor shaft
while applying DC24V
to the brake in case
of the motor with
electromagnetic brake.
• P.3-30 "Inputs and outputs on connector X4"
Measures
1) Check the setups of Pr3.02 to Pr3.03 again by
setting up Pr3.00 to 0, when you use the external
analog command.
2) Set up Pr3.04 to Pr3.07 and Pr3.08 to Pr3.11 by
setting up Pr3.00 to either one of 1, 2 or 3, when
you use the internal speed command.
1) Check and make wiring so as to connect speed
zero clamp input to COM–.
2) Set up Pr3.15.
1) Check that the input voltage is applied correctly by
setting up Pr3.17 to 0, when you use SPR/TRQR
input.
2) Check that the input voltage is applied correctly by
setting up Pr3.17 to 1, when you use the P-ATL/
TRQR input.
1) Set up the desired value to Pr3.21 by setting up
Pr3.17 to 0, when you use the parameter speed.
2) Check that the input voltage is applied correctly
by setting up Pr3.17 to 1, when you use the SPR/
TRQR/SPL input.
Check the wiring/voltage of main power of the driver
(L1, L2 and L3).
If you cannot turn the motor shaft, consult with the
dealer for repair.
1
2
3
4
5
6
7