CAUTION:
CAUTION: This equipment is designed to permit the connection of the earthed conductor of the DC supply circuit to the
earthing conductor at the equipment. If this connection is made, all the following must be met:
This equipment must be connected directly to the DC supply system earthing electrode conductor or to a bonding
jumper from an earthing terminal bar or bus to which the DC supply system earthing electrode conductor is connected.
This equipment must be located in the same immediate area (such as adjacent cabinets) as any other equipment that
has a connection between the earthed conductor of the same DC supply circuit and the earthing conductor, and also the
point of earthing of the DC system. The DC system must be earthed elsewhere.
The DC supply source is to be located within the same premises as the equipment.
Switching or disconnecting devices must not be in the earthed circuit conductor between the DC source and the point of
connection of the earthing electrode conductor.
DC power supply wire colors
DC power supply wire colors
Wire color
Wire color
Description
Description
Red
Positive return wire RTN
Black
Negative input wire -48V
Green + Yellow
Ground wire

Installing an AC power supply

Installing an AC power supply
Prerequisites
Prerequisites
Before installing a power supply option, review the Power supply warnings and cautions .
About this task
About this task
Wire slot
Wire slot
Safety ground