5. Press the Power On/Standby button.
For remote management, use the iLO virtual power button.
6. Configure the initial server setup.
7. Set up the storage .
8. Deploy an OS or virtualization software.
9. After the OS is installed, update the drivers.

Operational requirements

Operational requirements
When preparing the site and planning the installation for the HPE ProLiant DL325 Gen11 Server, be sure to observe the following general
operational requirements:

Space and airflow requirements

Temperature requirements
Power requirements
Electrical grounding requirements
For server-specific environmental requirements, see Environmental specifications.
Subtopics
Subtopics
Space and airflow requirements
Space and airflow requirements
Temperature requirements
Temperature requirements
Power requirements
Power requirements
Electrical grounding requirements
Electrical grounding requirements
Space and airflow requirements
Space and airflow requirements
To allow for servicing and adequate airflow, observe the following space and airflow requirements when deciding where to install a rack:
Leave a minimum clearance of 63.5 cm (25 in) in front of the rack.
Leave a minimum clearance of 76.2 cm (30 in) behind the rack.
Leave a minimum clearance of 121.9 cm (48 in) from the back of the rack to the back of another rack or row of racks.
Hewlett Packard Enterprise servers draw in cool air through the front door and expel warm air through the rear door. Therefore, the front
and rear rack doors must be adequately ventilated to allow ambient room air to enter the cabinet, and the rear door must be adequately
ventilated to allow the warm air to escape from the cabinet.
CAUTION: To prevent improper cooling and damage to the equipment, do not block the ventilation openings.
CAUTION:
When vertical space in the rack is not filled by a server or rack component, the gaps between the components cause changes in airflow
through the rack and across the servers. Cover all gaps with blanking panels to maintain proper airflow.
CAUTION: Always use blanking panels to fill empty vertical spaces in the rack. This arrangement ensures proper airflow.
CAUTION:
Using a rack without blanking panels results in improper cooling that can lead to thermal damage.
The 9000 and 10000 Series Racks provide proper server cooling from flow-through perforations in the front and rear doors that provide 64
percent open area for ventilation.