Procedure 3-2

Wiring the ac load box as a branch circuit

Use this procedure to wire the ac load box option as a branch circuit. Wire only
the option specified by the job requirements.
Load box wiring options
Branch circuit
Main service entrance panel
Tools required
Material required
Precautions
The following safety precautions should be observed at all times during the
cabinet installation procedures:
AccessNode Series 800A Outside Plant Cabinet Installation 323-3001-210 Issue 1.0
voltmeter
one medium flat blade screwdriver
one small flat blade screwdriver
one wire stripper for 6 AWG, 10 AWG and 12 AWG wire
one 2-inch NPT knockout connector or equivalent
No equipment should be installed until the cabinet is firmly secured to its
mounting pad, as described in Chapter 2, "Installing the cabinet".
Do not open the front or rear doors unless the cabinet is firmly secured to
the mounting pad.
Observe all NEC and local codes for electrical wiring.
CAUTION 1
Electrical shock hazard
The procedures listed in this chart should be done by a
qualified electrician. The procedures outlined are
recommended guidelines; be sure to follow all local codes
for wiring procedures.
—continued—
Connecting commercial power 3-7
Procedure
Procedure 3-2 on page 3-7
Procedure 3-3 on page 3-10