Procedure 7-3 (continued)
Routing the OSP fibers in split flex tubing to the FPP
Step
5
6
7
Figure 7-11
Routing patch cords to the ABM OC-3 or OC-12 cards
Rx
Tx
Insert approximately
1/2-inch (13 mm)
AccessNode Series 800A Outside Plant Cabinet Installation 323-3001-210 Issue 1.0
Action
Route the tubing to the front of the ABM shelf (see Figure 7-11).
Note: Maintain at least the minimum bend radius (3.0 inches/76 mm) for the
fiber pigtails or patch cords installed.
Insert 1/2-inch (13 mm) of one end of the tubing into the cable trough on the
top of the ABM shelf.
Extend the fiber patch cords along the cable trough at the top edge of the
ABM shelf as shown in Figure 7-11.
—continued—
Routing and splicing the fiber cable 7-25
FW-15310
FW-15310
ABM shelf
Swing frame
cutout
Tie-wrap
Spiral
wrap
tubing