Nortel SONET AccessNode 800A Series Manual page 332

Outside plant cabinet installation
Table of Contents

Advertisement

12-40 Cabinet maintenance operations
Procedure 12-11
Using the protector test access cord
This procedure explains the location of the protector test access cord and how
to use it.
Tools required
There are no special tools required to perform this procedure.
Action
Step
1
2
3
4
5
6
7
8
9
AccessNode 323-3001-210 Issue 1.0
Action
Open the termination door.
Engage the restrainer bar.
Note: The protector cord and test clip wires are located behind the swing
frame, at the top left side of SPC 5. The test clip wires are wrapped around a
mounting bracket (see Figure 12-9 on page 12-41).
Connect the test equipment to the station protector.
CAUTION
Service affecting procedure
This next step is service affecting. The customer is
disconnected and the line is dropped. Perform this
procedure during periods of low traffic.
Loosen the thumbscrews and open the SPC cover.
Remove the protector for the pair to be tested.
Plug the test cord in its place.
Replace the protector and SPC cover after the test.
Return the test cord to the mounting bracket.
Close the termination compartment doors.
—continued—