Nortel SONET AccessNode 800A Series Manual page 327

Outside plant cabinet installation
Table of Contents

Advertisement

Procedure 12-8
Connecting emergency standby power - attached
ac power pedestal option
This procedure explains how to attach the emergency generator power to the
S800A cabinet when the ac power pedestal is installed.
Each rectifier requires 2500 watts at 220 volts of emergency generator power.
Generators equipped with GFI protection can be used in this application; if the
GFI is disabled, the generator cannot be used.
The GFI is typical of small, noncommercial type generators.
Tools required
There are no special tools required to perform this procedure.
Action
Step
1
2
3
4
5
6
7
AccessNode Series 800A Outside Plant Cabinet Installation 323-3001-210 Issue 1.0
Action
Open the cabinet right side ac power pedestal door to fully engage the
restraining bar.
Turn the 60 A EMERGENCY circuit breaker located on the top center access
panel to the OFF position (see Figure 12-7 on page 12-37).
Actuate the knife switch lever to the CENTER OFF position.
Locate the emergency connector on the left side of the power pedestal (see
Figure 12-7 on page 12-37).
Use the AT&T-type #216 craft-access tool to unlock the tamper resistant
screw on the Hubbell connector locking collar.
Remove the locking cap.
Plug in the mating female Hubbell connector from the available generator and
screw in the locking collar.
Note: If desired, use the AT&T-type #216 craft-access tool to tighten the
tamper resistant screw on the Hubbell locking collar.
—continued—