12-56 Cabinet maintenance operations
Procedure 12-15 (continued)
Replacing the equipment fan shelves
Step
6
7
8
9
10
Equipment fan shelf
NT1W09AA
NT4K0610
NT1W09CA
11
12
13
14
AccessNode 323-3001-210 Issue 1.0
Action
Remove and save the shelf mounting screws at each end of the shelf that
secure the shelf to the swing frame.
Remove the fan shelf from the swing frame.
Place the new fan shelf in the vacated position.
Install the shelf mounting screws to secure the new shelf to the swing frame.
Connect the fan power connector to the fan shelf.
Note: For the location of the equipment fan shelf power connector, see one
of the figures listed in the table below:
Install the fan shelf cover panel.
Turn the CU A or CU B BIP circuit breaker (see step 3) to the ON position.
Verify that the RED alarm LED is extinguished.
Close the swing frames and the cabinet doors.
—end—