Cautions
Observe the following cautions while you perform the procedures in this
chapter.
AccessNode Series 800A Outside Plant Cabinet Installation 323-3001-210 Issue 1.0
CAUTION 1
Electrical shock hazard
Disconnect any unused battery cables from the NT1W64AA
battery breaker panel adapter to prevent potential electrical
shock, equipment shorting, or both.
CAUTION 2
Battery string minimum requirements
Always install a minimum of three battery strings to evenly
distribute the charge current among the circuit breakers of
the battery breaker panel (BBP).
CAUTION 3
Battery replacement requirements
Do not replace individual battery packs. When one or more
battery packs in the same string fail, replace all packs in that
string with matched batteries having similar date codes.
CAUTION 4
Fire hazard
Remove all paper and any other combustible materials from
inside a cabinet before the cabinet is powered up. Failure to
comply with this warning can cause a fire.
CAUTION 5
Air flow requirement
Do not remove the air flow baffle installed in the electronics
compartment. The air flow baffle directs air flow through the
cabinet. The air flow baffle must be installed at all times
during the operation of the cabinet.
Do not store objects, combustible or otherwise, in the
cabinet as this can disrupt air flow.
Installing and connecting the batteries 9-3