14 TROUBLESHOOTING
Relevant buffer memory address
Axis 1
Axis 2
Axis 3
18
168
318
19
169
319
20
170
320
21
171
321
22
172
322
23
173
323
24
174
324
25
175
325
26
176
326
27
177
327
28
178
328
29
179
329
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Setting range
(Setting given in sequence program)
(In standard mode)
• [mm] [inch] [pulse]
-2147483648 to 2147483647
• [degree] 0 to 35999999
(In stepping motor mode)
• [mm] [inch] [pulse]
–134217728 to 134217727
• [degree] 0 to 35999999
0, 1
0, 1
(In standard mode)
• [mm] [inch] [pulse]
1 to 32767000
• [degree] 1 to 32767
(In stepping motor mode)
• [mm] [inch] [pulse]
1to 2047937
• [degree] 1 to 2047
1 to 500
0, 1
0, 1
0, 1
0, 1, 2
0: Manual pulse generator operation
ignored
1: Manual pulse generator connected to
axis 1 is used.
2: Manual pulse generator connected to
axis 2 is used.
3: Manual pulse generator connected to
axis 3 is used.
14 - 23
Remedy
• Change the setting to within the setting range.
• Change the settings so that the lower limit value is
smaller than the upper limit value with a unit other
than "degree."
Change the setting to within the setting range and turn
OFF then ON the PLC READY signal (Y1D).
MELSEC-A