8 ZERO POINT RETURN CONTROL
Zero point signal
Torque limit
Machine zero point return start
(Positioning start signal)
Zero point return request flag
[ Md.40 Status : b3]
Zero point return complete flag
[ Md.40 Status : b4]
Deviation counter clear output
Md.35 Axis operation status
Md.44 Movement amount
after near-point dog ON
Md.29 Current feed value
Md.30 Machine feed value
Fig. 8.10 When the zero point signal is input before the stop at the stopper
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Restrictions
(1) Always limit the servomotor torque after the " Pr.49 Creep speed" is reached.
If the torque is not limited, the servomotor may fail when the machine presses
against the stopper. (Refer to section "12.4.2 Torque limit function".)
(2) The zero point retry function cannot be used in "stopper stop method 3)".
Precautions during operation
(1) If the zero point signal is input before the workpiece stops at the stopper, the
workpiece will stop at that position, and that position will become the zero
point. At this time, an error will not occur.
V
Valid torque limit range
ON
OFF
ON
OFF
OFF
In zero point return
Standing by
Inconsistent
0
Inconsistent
Value the machine moved is stored
(2) If the restart command is turned ON after machine zero point return is stopped
upon a stop signal, an error "zero point return restart not possible" (error code:
209) occurs.
Pr. 49 Creep speed
8 - 15
MELSEC-A
Stopper
t
ON
Standing by
Zero point address