HindlePower Inc
•
Ethernet Communications Adapter (A22) – optional
•
Eliminator Capacitor (C2) – optional
•
AC Input Circuit Breaker
•
DC Output Circuit Breaker
•
Main Filter Inductor
•
Secondary Filter Inductor
•
Power Isolation Transformer
For detailed component location and orientation, refer to the Style-5054 Internal Component
Layout Drawings
(JE5252-01
Rectifier Assembly (A6)
Rectifier Assembly (A6)
This is a grouping of an aluminum heatsink and a Silicon-Controlled Rectifier (SCR) module. It is
mounted on the left side of ATevo in Style-5054 enclosures. The Rectifier (A6) converts single-
phase alternating current (ac) power to direct current (dc) for the battery.
Remote Temperature Probe (A10) – optional
Remote Temperature Probe (A10) – optional
The battery temperature compensation, or 'TempCo', probe (A10) contains a temperature-
dependent resistor in an epoxy module. When used, this probe is installed on the battery and is
connected to the Power Board (A2) at TB8.