4.10.1. Setting Up Ground Fault Alarm
Setting Up Ground Fault Alarm
Sensitivity
Sensitivity
To change the resistance values (measured in kOhm) of the ground fault alarm sensitivities,
press MENU, then select GROUND ALARM.
• Navigate to Gr
Ground F
ound Fault W
• Select it with EDIT/ENTER.
• Press UP and DOWN to change setting value.
• Once desired setting is displayed, press EDIT/ENTER to store it.
• Repeat process for Gr
*
To increase the ground alarm sensitivity, lower the kOhm value. To decrease the
sensitivity, raise the kOhm value.
Copyright HindlePower Inc. 2021
ault War arning
ning using UP and DOWN.
Ground F
ound Fault Critical
ault Critical.
ATevo O&SI - 1PH Input Group I (6-25 Adc) - 1.1_en