HindlePower ATevo Series Operating/Service Instructions Manual page 118

Hide thumbs Also See for ATevo Series:
Table of Contents

Advertisement

HindlePower Inc
4.9.
4.9. Enabling/Disabling High Level
Enabling/Disabling High Level
Detect
Detect
ATevo has a dedicated hardware circuit that can shut down the charger should a catastrophic
microprocessor failure occur and the rectifier control become locked to the full 'on' state.
The setting for the Analog High Voltage Shutdown jumper determines whether the High Level
Detect circuit is enabled or disabled.
The High Voltage Shutdown jumper (J1) is located center right on the Main Control Board (A1).
To change the enable/disable status of the High Level Detect circuit:
1. Turn OFF (open) both AC Input (CB1) and DC Output (CB2) Circuit Breakers.
2. Open the ATevo front panel door.
3. Locate the Main Control Board (A1) on back of the door.
4. Locate jumper (J1) labeled 'High Level Detect Shutdown' on the center right of the Main
Control Board (A1).
5. Move jumper shorting block as follows:
a. 'EN' to enable the High Level Detect Shutdown
b. 'DIS' to disable the High Level Detect Shutdown
6. Close the front panel door.
7. Turn ON (close) both Circuit Breakers (CB1/CB2).
See
Section 5.4
for more information on the High Level Detect feature.
Copyright HindlePower Inc. 2021
ATevo O&SI - 1PH Input Group I (6-25 Adc) - 1.1_en
Last modified: 3 August 2023
Page 118 of 316