PROCEDURE
PROCEDURE
1. Use a dc disconnect switch or circuit breaker between ATevo and the dc bus. This device
should have lockout capability to allow ATevo to be disconnected from the dc bus for
maintenance.
2. Remove safety shield (see
3. Run dc wiring to Output Circuit Breaker (CB2).
4. Connect wires to appropriate locations on the DC Output Breaker (CB2+/-) as indicated on
drawing above.
5. Using a flat-blade screwdriver, securely tighten compression screws on DC Output Breaker
Terminals (CB2+/-).
6. Reinstall safety shield after you have made and checked all connections.
Copyright HindlePower Inc. 2021
Section 2.2, Removing Protective Safety
ATevo O&SI - 1PH Input Group I (6-25 Adc) - 1.1_en
Shield).
Last modified: 3 August 2023