12.6.7. Analog Input Action Assignment

Analog Input Action Assignment
The Analog Input Action assignment links the analog input alarm to a charger control. Examples
of a charger control include charger shutdown or float/equalize mode control. ATevo will
execute the charger control when the analog input alarm is in the active state.
To assign a control to an analog input:
MENU > AUX INPUTS > 'Analog Input Configuration' > select input (refer to
'Action:' > select action
*
Midway through 2021, ATevo chargers began shipping with firmware v2.7.0 which
includes a new action called "Disable Equalize" which is described further in the
Appendix topic, Firmware v2.7.0 Enhancements.