HindlePower ATevo Series Operating/Service Instructions Manual page 207

Hide thumbs Also See for ATevo Series:
Table of Contents

Advertisement

HindlePower Inc
11.2.
11.2. Remote Sense Connection
Remote Sense Connection
Remote sensing:
• Compensates for voltage drop in dc wiring between ATevo and the battery.
• Directly monitors battery or dc bus voltage. The front panel meter displays actual voltage
at the battery or dc bus.
SCHEMATIC
SCHEMATIC
To wire ATevo for remote sensing, install twisted-pair cabling from the remote sense terminals
to the battery terminals or dc bus. ATevo control circuitry measures dc voltage at the battery
terminals and controls charger output to maintain battery voltage at the desired float or
equalize voltage.
ATevo cannot protect against short circuits in remote sense wiring. Install a
1.0A fuse at the battery or dc bus end of each remote sense cable.
Copyright HindlePower Inc. 2021
ATevo O&SI - 1PH Input Group I (6-25 Adc) - 1.1_en
Last modified: 3 August 2023
Page 207 of 316