ATevo O&SI - 1PH Input Group I (6-25 Adc) - 1.1_en
16.1.
16.1. Alarm Triggers
Alarm Triggers
The Evo charger always had the user configurable "Common Alarm". New alarms named "High
Priority Alarm" and "Low Priority Alarm" are now available to a user who wishes to further
customize alarm priority. These alarms can be configured to close a relay on an AUX I/O and are
also readable over SCADA. Configuration is enhanced to accommodate selecting the triggers
for these new alarms in the same menu that the common alarm is configured.
Firmware prior to v2.7.0 navigated directly to common alarm configuration. Firmware v2.7.0 now
navigates to a menu that allows a user to select one of the three "aggregate" alarms to configure.
The lower right display shown is typical when "Common Alarm" has been selected. "High Priority
Alarm" and "Low Priority Alarm" displays are similar. Also new in v2.7.0 is that alarms are listed in
alphabetical order. In addition, alarm types that depend on optional hardware are only displayed if