Disabling Ground Detection - HindlePower ATevo Series Operating/Service Instructions Manual

Hide thumbs Also See for ATevo Series:
Table of Contents

Advertisement

HindlePower Inc
5.5.

5.5. Disabling Ground Detection

Disabling Ground Detection
Depending on installation, users may wish to temporarily (or permanently) disable the ATevo
ground detect feature. If so:
1. Shut down ATevo, and allow internal voltages to dissipate.
2. Open the ATevo front panel door, and remove the safety shield.
3. Locate the Power Board (A2).
4. Identify the 3-pin shorting block (JP102), marked 'GROUND DETECT' on A2.
5. Move the 2-pin jumper from the ENABLED to DISABLED position.
6. Restart ATevo with ground detection disabled.
Copyright HindlePower Inc. 2021
ATevo O&SI - 1PH Input Group I (6-25 Adc) - 1.1_en
Last modified: 3 August 2023
Page 137 of 316

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ja5011-51

Table of Contents