• Plug the quick-connect terminal attached to the end of the TempCo cable's shield wire
onto the Power Board's EARTH terminal.
• Connect the quick-connect terminal removed from the EARTH terminal to the 'piggy-back'
terminal on the end of the TempCo cable's shield wire.
• Fasten the TempCo cable to existing wire harness with plastic wire ties.
12. At the battery, connect the quick-connect terminals to the TempCo probe (A10).
Connection points are not polarity sensitive.
13. Coil up and wire-tie any excess wire to prevent damage.
14. Confirm that:
• All connections are secure.
• Both the TempCo shield and the original ground wire are connected to the EARTH quick-
connect terminal (A2-EARTH).
• The twisted-pair wires of the TempCo cable are connected to the 2-position terminal block
on the Power Board (A2-TB8).
15. Replace the safety shield and close the front panel door.
16. Restart the ATevo.
10.2.1 Configuring the TempCo Option
10.2.1 Configuring the TempCo Option
ATevo will need to be configured to enable the TempCo probe (A10) and to select the battery
type. Refer to
Section 4.11 Configuring Battery Settings