12.6.4.
12.6.4. Analog Input Scaling
Analog Input Scaling
Assignment
Assignment
ATevo can scale the analog input values such that the measurement can be represented in
primary units.
To adjust the scaling, enter the primary value when the analog input is at 0 V, and the primary
value when the analog input is 10.0 Vdc. ATevo will report the measurements and adjust the
alarm thresholds in true primary units.
To change the low scale value:
MENU > AUX INPUTS > 'Analog Input Configuration' > select input (refer to
'0V=:' > set desired digits
*
This number must represent the primary value when the input value is 0 V. If no
scaling is required, set 0.
To change the high scale value assigned to the analog input:
'10V=:' > set desired digits
*
This number must represent the primary value when the input value is 10.0 Vdc.
If no scaling is required, set 10.
Copyright HindlePower Inc. 2021
ATevo O&SI - 1PH Input Group I (6-25 Adc) - 1.1_en