7.1.
7.1. Legacy AT10.1 Alarms & Indicators
Legacy AT10.1 Alarms & Indicators
ATevo alarms can be divided into two (2) groups:
• Legacy AT10.1 Alarms
• Advanced Alarms (covered in
The Legacy Alarm group is a superset of the standard alarm group recommended by the
NEMA-PE5 and IEEE standards for stationary battery char
front panel LED indicators and are referred to as 'legacy'
functionality as the standard alarms available on legacy AT10.1 and AT30 Series battery
chargers.
The GREEN AC ON LED indicator, and the six (6) RED Legacy Alarm LED indicators are
summarized in the table in
The table identifies:
• alarm active while LED is lit
• condition that is detected
• possible causes of the condition (where applicable)
• configurable set point that controls when alarm becomes active (where applicable), and
section where such configuration is discussed
• relay which alarm activates
*
All Legacy Alarms will activate the Common Alarm relay (as discussed in Section
7.2), thereby changing to the alarmed state after a configured time delay.
Alarms will also be reported by any installed optional protocol communications board and may
also be configured to activate a discrete relay on optional Auxiliary I/O Boards.
gives instructions on how to configure relays.
Copyright HindlePower Inc. 2021
Section
7.5)
stationary battery chargers
Section
7.3.
ATevo O&SI - 1PH Input Group I (6-25 Adc) - 1.1_en
gers. These alarms have dedicated
'legacy' alarms since they have the same
Last modified: 8 September 2023
Section 12.4
Page 166 of 316