10.1.
10.1. ATevo Battery Temperature
ATevo Battery Temperature
Compensation
Compensation
Battery manufacturers specify recommended float and equalize voltages at 25 °C (77 °F) for
their product. Temperatures above or below the nominal
voltages (respectively), in order to prolong battery life and ensure reliable operation. The ATevo
Battery Temperature Compensation (or TempCo) option automatically adjusts the charger's dc
output voltage, based upon battery temperature. In addition to the voltage compensation
feature, the battery probe also allows ATevo to provide battery temperature monitoring, and a
battery over-temp alarm.
The ATevo TempCo option (ordering p/n EJ5304-##) consists of a bagged kit, including a
Battery Temperature Probe (A10), and a signal cable to connect the probe to the ATevo. The
A10 probe contains a temperature-dependent resistor in an epoxy module, that is installed on
(or near) the battery. The TempCo option can be purchased with ATevo, or field installed later.
The bagged TempCo accessory also contains a separate user Installation & Operating
Instructions (p/n JA5015-51). An abbreviated version of that text is listed in the following
sections.
Copyright HindlePower Inc. 2021
ATevo O&SI - 1PH Input Group I (6-25 Adc) - 1.1_en
nominal 25 °C require a slightly lower or higher